Energy, Exergy and Economic Analysis of Absorption Chiller Systems: A Case Study for a Wood Pencil Factory


Şahin A., Özdemir M. R.

International Journal of Renewable Energy Research-IJRER, cilt.11, sa.4, ss.1469-1477, 2021 (ESCI) identifier identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 11 Sayı: 4
  • Basım Tarihi: 2021
  • Dergi Adı: International Journal of Renewable Energy Research-IJRER
  • Derginin Tarandığı İndeksler: Emerging Sources Citation Index (ESCI), Scopus
  • Sayfa Sayıları: ss.1469-1477
  • Anahtar Kelimeler: Absorption chiller, Waste heat recovery, Energy analysis, Exergy analysis, Economic analysis, CYCLE
  • Marmara Üniversitesi Adresli: Evet

Özet

This study examines the use of absorption chiller systems in a designated industrial facility having waste heat by conducting energy, exergy and economic analyses. The absorption chiller systems namely single-effect, double-effect series, double-effect parallel and double-effect reverse parallel were analysed to determine the best alternative for the wood pencil factory. The results indicated that the COP of the single-effect absorption chiller systems is changed from 0.758 to 0.763 when the temperature of the generator was increased from 89 degrees C to 125 degrees C. However, the exergetic performance of the single-effect absorption chiller system decreased by 40% in the same generator temperature range. On the other hand, COP of all double-effect absorption chiller systems increased about 8 % when the generator temperature was changed from 116 degrees C to 155 degrees C while the exergetic performance of all double absorption chiller systems decreased by around 14% for the same generator temperature range. The COP and exergetic efficiency values of the double-effect parallel system were found to be higher than other absorption systems at all generator temperature values. Overall, this study recommends that the double-effect parallel absorption chiller systems can be preferred for the factories having waste heat source wood chips. The average payback period of the system was also found to be 1.4 years. Furthermore, this study shows that double-effect parallel absorption chiller systems can be proposed for the facilities having wood chips waste sources instead of double-effect reverse parallel absorption chiller systems since they are easy to operate and have lower maintenance costs.